Minimum velocities of air in extraction systems:

The smaller values are only applicable in pipe systems with a very gentle air flow – bends with big radius, forks with small angle, short or vertical pipe lines.

Scope-woodworking:

Wood chips 25-30 m/s
Sawdust, damp 22-24 m/s
Thick wood chips 18-22 m/s
Wood wool 18-20 m/s
Little shavings 16-18 m/s
Finest wood dust 12-14 m/s