Minimum velocities
of air in extraction systems:
The smaller values
are only applicable in pipe systems with a very gentle air flow bends
with big radius, forks with small angle, short or vertical pipe lines.
Scope-woodworking:
Wood chips 25-30
m/s
Sawdust, damp 22-24 m/s
Thick wood chips 18-22 m/s
Wood wool 18-20 m/s
Little shavings 16-18 m/s
Finest wood dust 12-14 m/s